HVAC · VENTILATION · MAINTENANCE

Residential · Case Study

Daikin VRV Fault Diagnosis – Villa in Al Safa, Dubai

Al Safa, Dubai·Daikin VRV fault diagnosis, 2 systems (U7 and LC25 errors)
Client type
Villa
Location
Al Safa, Dubai
System type
Daikin VRV (2 outdoor systems)

Project overview

On 16 April 2026 AGEC visited a villa in Al Safa, Dubai for a VRV unit inspection. The villa is cooled by two Daikin VRV outdoor systems: model RXYTQ14T7YF (System 1) and model RXYTQ12T7YF (System 2). Each system has a master and a slave outdoor module.

This is a diagnosis case study: it records what we found and what we recommended, not a completed repair.

Project at a glance

  • 2

    Daikin VRV systems in fault

  • U7 and LC25

    Error codes (LC25 as recorded on site)

  • 397 V

    Supply, measured with a clamp meter

  • 39 V

    Earth to neutral, measured with a clamp meter

The challenge

Two Daikin VRV systems in one villa were in fault at the same time. System 1 showed a U7 error on the controller, and System 2 showed LC25 (as recorded on site). The job was to trace each code to the outdoor module behind it and keep the healthy modules running.

What we found

System 1: RXYTQ14T7YF, U7 error

  • The controller showed a U7 error.
  • On checking the outdoor units, slave module (1) had no power.

System 2: RXYTQ12T7YF, LC25 (as recorded on site)

  • The controller showed LC25, as recorded on site.
  • On the outdoor unit, slave (1) fan PCB (1) and (2) were burnt, and fan motor (1) was defective.

Electrical readings

  • Supply: 397 V.
  • Earth to neutral: 39 V.
  • Both were measured on site with a clamp meter.

How we kept the villa cooling

In both systems we isolated the faulty slave module and ran the healthy modules.

System 1

  • Isolated slave (1) and ran the master unit, so the system kept cooling.

System 2

  • Isolated slave (1) and ran the master and slave (2).

Our recommendation

System 1

  • The electrical team to check the supply to slave (1).

System 2

  • Replace fan PCB (1) and (2) and fan motor (1).

Both systems

  • The electrical team to check the power supply and the earth/neutral connection.
Burnt fan PCB found in the slave outdoor module of a Daikin VRV system
Burnt fan PCB found in the slave outdoor module (System 2)
Nameplate of a Daikin RXYTQ14T7YF VRV outdoor unit, System 1, with the serial number pixelated
System 1: Daikin RXYTQ14T7YF nameplate (serial number blurred)
Nameplate of a Daikin RXYTQ12T7YF VRV outdoor unit, System 2, with the serial number pixelated
System 2: Daikin RXYTQ12T7YF nameplate (serial number blurred)
AC clamp meter display showing a supply reading of 397 V
Supply: 397 V on the clamp meter
AC clamp meter display showing an earth-to-neutral reading of 39 V
Earth to neutral: 39 V on the clamp meter

Related services

Faults like these are what our VRF maintenance and AC repair services deal with.

VRV error code or a system in fault? Contact AGEC